  • 01/05/2017

    pros Good quality and good accuracy. Test it at 12 and 24 volt . there is small difference 0.05ma the indication with my multimeter but maybe it's the multimeter fault. the range is from 3,9 to 21ma with 10 turns of a potentiometer. cons The potentiometer needs glue to secure it to the board because with small force disconnect from his base. The display indication is not the real output current because it always has a value even if the output cable is disconnected. So if you want to check if there is a disconnection in a line you have to install multimeter in output. Careful. if the signal has common ground with the power supply when connect the cables connect last the signal cable and when disconnect remove first the signal cable. If you remove first the grd of power supply the display turn off but I measure 42 ma in output (with 24v power and 330 Ω load).

    Comentarios
    Mostrar original
  • 20/03/2018

    I bought five of these and measured their outputs (4.0 mA, 10 mA, 12 mA and 20 mA) across a 100 ohm 0.1% tolerance resistor with a decent DVM. The biggest deviation was 0,3 mA at an indicated 20 mA output. Most were within 0.1 mA of the displayed output.

    Comentarios (1)
    Mostrar original
  • 20/08/2018

    Bom gerador para quem trabalha com simulação em instrumentação

    Comentarios
    Mostrar original
  • 20/11/2017

    Works perfect and exact! I recommend this on. Make a box i 3D for it and you have the perfect test instrument for your experiments.

    Comentarios
    Mostrar original
  • 16/08/2017

    works as expected

    Comentarios
    Mostrar original
  • 08/06/2017

    Display set to 4.0 mA Measured value is 3.66 mA Display set to 8.0mA Measured value is 7.55mA Display set to 12.0 mA Measured value is 11.56 mA Display set to 16.0 mA Measured value is 15.48 mA Display set to 20.0 mA Measured value is 19.33 mA

    Comentarios (1)
    Mostrar original
  • 14/07/2020

    Muy bien, como acordamos.

    Comentarios
    Mostrar original
  • 19/06/2020

    ¡Ser bueno!

    Comentarios
    Mostrar original
  • 02/06/2020

    perfecto para simular sensores industriales en un bucle de 4-20ma . Caso de impresión 3D disponible señor cosa.

    Comentarios
    Mostrar original
  • 31/01/2019

    Works as expected, will buy some more for the team!

    Comentarios
    Mostrar original
Show:

    Total 0 paginas

    Ir a la pagina

    recommendation for you
    • US$10.40
    • US$15.99
    • US$11.99
    • US$5.99
    • US$21.84
    • US$29.93
    • US$14.42
    • US$11.99
    • US$8.19
    • US$9.99
    • US$38.99
    • US$323.00
    • US$34.49
    • US$105.99
    • US$16.59
    • US$13.79
    • US$4.99
    • US$48.99